    Product Description

    Digital electronic module with four outputs
    Output current 0.5 A per output
    Rated load voltage 24 VDC
    Short-circuit protection
    Suitable for solenoid valves, DC contactors, and indicator lights
    Extended temperature range from 0 to 55 °C with vertical installation

    Rated load voltage L+ (from the power module) 24 VDC
    Reverse polarity protection Yes1
    Total current of the outputs (per module) 2 A
    Electrical isolation
    Between the channels No
    Between the channels and backplane bus Yes
    Permissible potential difference
    Between the different circuits 75 VDC / 60 VAC
    Insulation tested 500 VDC
    Current consumption
    From the load voltage L+ (no load) Max. 5 mA per channel
    Power dissipation of the module Typically 0.8 W
    Status, interrupts, diagnostics
    Status display Green LED per channel
    Diagnostics function No
    Data for selecting an actuator
    Output voltage
    At signal "1" Min. L+ (-1 V)
    Output current
    At signal "1"
    – Rated value
    0.5 A
    – Permitted range
    7 mA to 0.6 A
    With signal "0" (leakage current) Max. 0.3 mA
    Output delay (for resistive load)
    At "0" to "1" Max. 100 μs
    At "1" to "0" Max. 300 μs
    Load resistor range 48 Ω to 3.4 kΩ
    Lamp load Max. 5 W
    Connecting two outputs in parallel
    For redundant triggering of a load Yes (per module)
    To increase performance No
    Control of a digital input Yes
    Switch rate
    For resistive load 100 Hz
    On inductive load 2 Hz
    For lamp load 10 Hz
    Limitation (internal) of the voltage induced on
    circuit interruption
    Typically L+ (-55 V to -60 V)
    Reverse-voltage proof Yes, if using the same load voltage as at the
    power module2
    Short-circuit protection of the output Yes3