Product Description
Mersen 9F60CMJ905 Medium Voltage IEEE Transformer Fuse 25.8KV - 0.5E
Mersen fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interruPotential Transforming rating. These fuses are designed to withstand the transformer magnetizing inrush current. They have 2" (size C), 3" (size D) and 2x3" (size DD) inch diameter barrels with ferrules and are mounted in spring reinforced clips.
Features:
Ferrule mounting for standard clips and interchangeability with other brands of fuses.
Current-limiting for superior equipment protection.
Non-venting for silent operation
Metal embossed catalog number and manufacturing date for lasting identification.
Outdoor usage for the type EJO.
Blown-fuse indicator to give positive identification of open fuse: 9F60: 0.125 lb tripped force – 0.20 Inch
Application: Protection for 16 kV to 25 kV transformers or distribution systems.
Current Rating: 0.5 A
Diameter: 2x3
Height: 6.16
Length: 30.81
Material, Body: Epoxy
Material, Contact: Silver-Plated Copper
Primary Type: Ferrule
Series: Amp-Trap 9F60/9F62 Series
Termination: Ferrule
Type: E-Rated
Voltage Rating: 25.8 kV
Weight: 29
Width :6.16