Product Description
Equipped with the RUN output for checking the operation status, as well as the replacement notification function for easy maintenance
Supply voltage    100 to 240 V AC (wide-range), 50/60 Hz
Operating voltage andfrequency ranges    85 to 264 V AC, 47 to 63 Hz
Power consumption    100 VA max.    
Inrush current 1    At 100 to 120 V AC: 15 A/8 ms max. for cold start at room temperatureAt 200 to 240 V AC: 30 A/8 ms max. for cold start at room temperature    
Output capacity 7   5.0 A, 5 V DC (including supply to CPU Unit)     0.8 A, 24 V DC    Total: 25 W max.    
RUN output 2    Contact configuration: SPST-NOSwitch capacity:250 V AC, 2 A (resistive load)120 V AC, 0.5 A (inductive load),24 V DC, 2A (resistive load)24 V DC, 2 A (inductive load)    
Insulation resistance    20 MΩ min. (at 500 V DC) betweenAC external and GR terminals 3        
Dielectric strength 4    2,300 V AC 50/60 Hz for 1 minbetween AC external and GRterminals 3 Leakage current:  
Noise immunity    2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistance    Conforms to IEC60068-2-65 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 HzAcceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min)
Shock resistance    Conforms to IEC60068-2-27147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operatingtemperature    0 to 55 ° C
Ambient operatinghumidity    10% to 90% (with no condensation)        
Atmosphere    Must be free from corrosive gases.
Ambient storagetemperature    - 20 to 70 ° C (excluding battery)        
Grounding    Less than 100 Ω
Enclosure    Mounted in a panel.
     					
     					