Product Description
Equipped with the RUN output for checking the operation status, as well as the replacement notification function for easy maintenance
Supply voltage 100 to 240 V AC (wide-range), 50/60 Hz
Operating voltage andfrequency ranges 85 to 264 V AC, 47 to 63 Hz
Power consumption 100 VA max.
Inrush current 1 At 100 to 120 V AC: 15 A/8 ms max. for cold start at room temperatureAt 200 to 240 V AC: 30 A/8 ms max. for cold start at room temperature
Output capacity 7 5.0 A, 5 V DC (including supply to CPU Unit) 0.8 A, 24 V DC Total: 25 W max.
RUN output 2 Contact configuration: SPST-NOSwitch capacity:250 V AC, 2 A (resistive load)120 V AC, 0.5 A (inductive load),24 V DC, 2A (resistive load)24 V DC, 2 A (inductive load)
Insulation resistance 20 MΩ min. (at 500 V DC) betweenAC external and GR terminals 3
Dielectric strength 4 2,300 V AC 50/60 Hz for 1 minbetween AC external and GRterminals 3 Leakage current:
Noise immunity 2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistance Conforms to IEC60068-2-65 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 HzAcceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min)
Shock resistance Conforms to IEC60068-2-27147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operatingtemperature 0 to 55 ° C
Ambient operatinghumidity 10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gases.
Ambient storagetemperature - 20 to 70 ° C (excluding battery)
Grounding Less than 100 Ω
Enclosure Mounted in a panel.