Product Description
2 inputs for measuring voltage
Input ranges:
± 10 V, resolution 13 bits + sign
± 5 V, resolution 13 bits + sign
1 V to 5 V, resolution 13 bits
Isolated from the load voltage L+
Permissible common mode voltage 2 VACSS
Extended temperature range from 0 to 50°C with vertical installation
Supports isochronous operation No
Number of inputs 2
Cable length
Shielded Max. 200 m
Parameter length 4 bytes
Address space 4 bytes
Voltages, currents, potentials
Rated load voltage L+ (from the power module) 24 VDC
Reverse polarity protection Yes
Electrical isolation
Between the channels and backplane bus Yes
Between the channels and load voltage L+ Yes
Between the channels No
Permissible potential difference
Between the inputs and MANA (UCM) 2 VACSS
Between MANA and the central grounding point
(UISO)
75 VDC / 60 VAC
Insulation tested 500 VDC
Current consumption
From load voltage L+ Max. 30 mA
Power dissipation of the module Typically 0.6 W
Status, interrupts, diagnostics
Diagnostics function
Group error Red "SF" LED
Diagnostic functions readable Yes
Analog value generation
Measuring principle Integrative
Integration and cycle time/resolution per channel:
Integration time can be assigned parameters YeInterference frequency suppression in Hz 60 50
Integration time in ms 16,7 20
Conversion time in ms 55 65
Cycle time in ms Number of active channels per module x
conversion time
Resolution (including overshoot range) ± 10 V/13 bits + sign
± 5 V/13 bits + sign